Watts to amps chart (120 V and 240 V)
For heaters, lights and other loads with a power factor of 1. Motors draw a little more; see the formulas below.
| Watts | Amps at 120 V | Amps at 240 V | Amps at 12 V DC |
|---|---|---|---|
| 100 W | 0.83 | 0.42 | 8.33 |
| 200 W | 1.67 | 0.83 | 16.7 |
| 300 W | 2.5 | 1.25 | 25 |
| 400 W | 3.33 | 1.67 | 33.3 |
| 500 W | 4.17 | 2.08 | 41.7 |
| 600 W | 5 | 2.5 | 50 |
| 700 W | 5.83 | 2.92 | 58.3 |
| 750 W | 6.25 | 3.13 | 62.5 |
| 800 W | 6.67 | 3.33 | 66.7 |
| 900 W | 7.5 | 3.75 | 75 |
| 1,000 W | 8.33 | 4.17 | 83.3 |
| 1,200 W | 10 | 5 | 100 |
| 1,500 W | 12.5 | 6.25 | 125 |
| 1,800 W | 15 | 7.5 | 150 |
| 2,000 W | 16.7 | 8.33 | 166.7 |
| 2,400 W | 20 | 10 | 200 |
| 2,500 W | 20.8 | 10.4 | 208.3 |
| 3,000 W | 25 | 12.5 | 250 |
| 3,500 W | 29.2 | 14.6 | 291.7 |
| 4,000 W | 33.3 | 16.7 | 333.3 |
| 4,500 W | 37.5 | 18.8 | 375 |
| 5,000 W | 41.7 | 20.8 | 416.7 |
How many amps is 1,500 watts?
1,500 W is 12.5 A at 120 V, 6.25 A at 240 V and 125 A from a 12 V battery through an inverter (before the inverter's own losses). It is the top of the range for plug-in space heaters (750 to 1,500 W) and the kettle in DOE's own worked example. At 12.5 A it sits above the 12 A that one plug-in appliance may use on a 15 A circuit, and run for 3 hours or more it needs 15.6 A of breaker, so a 20 A circuit with nothing else on it.
Amps to watts
Watts = amps x volts (x power factor on AC motor loads).
| Amps | Watts at 120 V | Watts at 240 V | Watts at 12 V DC |
|---|---|---|---|
| 1 A | 120 | 240 | 12 |
| 2 A | 240 | 480 | 24 |
| 5 A | 600 | 1,200 | 60 |
| 8 A | 960 | 1,920 | 96 |
| 10 A | 1,200 | 2,400 | 120 |
| 12 A | 1,440 | 2,880 | 144 |
| 15 A | 1,800 | 3,600 | 180 |
| 16 A | 1,920 | 3,840 | 192 |
| 20 A | 2,400 | 4,800 | 240 |
| 24 A | 2,880 | 5,760 | 288 |
| 25 A | 3,000 | 6,000 | 300 |
| 30 A | 3,600 | 7,200 | 360 |
| 40 A | 4,800 | 9,600 | 480 |
| 50 A | 6,000 | 12,000 | 600 |
How many watts can a 15 or 20 amp circuit handle?
A 15 A circuit at 120 V carries 1,800 W at most, and 1,440 W (12 A) for a load that runs 3 hours or more. A 20 A circuit carries 2,400 W, or 1,920 W (16 A) for a continuous load. Everything plugged into the same circuit adds up, including the lamps and chargers you forget about.
| Breaker | 120 V, full | 120 V, 80% | 240 V, full | 240 V, 80% |
|---|---|---|---|---|
| 15 A | 1,800 W | 1,440 W | 3,600 W | 2,880 W |
| 20 A | 2,400 W | 1,920 W | 4,800 W | 3,840 W |
| 30 A | 3,600 W | 2,880 W | 7,200 W | 5,760 W |
| 40 A | 4,800 W | 3,840 W | 9,600 W | 7,680 W |
| 50 A | 6,000 W | 4,800 W | 12,000 W | 9,600 W |
80% is the same limit as the NEC's 125% rule turned around: a breaker rated at least 125% of the load means the load stays at or under 80% of the breaker.
Common appliance amps
Running watts from manufacturer generator wattage guides (the top of the range where a guide gives one), divided by the voltage the appliance runs on. Compressors and pumps draw more for a moment as they start; the generator size calculator lists starting watts. The nameplate on your appliance gives its own figure.
| Appliance | Running watts | Volts | Amps |
|---|---|---|---|
| Refrigerator | 400 | 120 | 3.33 |
| Microwave (1,000 W) | 1,500 | 120 | 12.5 |
| Coffee maker | 1,200 | 120 | 10 |
| Space heater | 1,500 | 120 | 12.5 |
| Window AC (5,000 BTU) | 600 | 120 | 5 |
| Window AC (10,000 BTU) | 1,500 | 120 | 12.5 |
| Sump pump (1/2 hp) | 1,050 | 120 | 8.75 |
| Washing machine | 1,000 | 120 | 8.33 |
| TV (flat screen) | 190 | 120 | 1.58 |
| Garage door opener | 720 | 120 | 6 |
| RV air conditioner (13,500 BTU) | 1,800 | 120 | 15 |
| Electric clothes dryer | 5,400 | 240 | 22.5 |
| Electric water heater | 4,500 | 240 | 18.8 |
| Electric range burner (8 in) | 2,100 | 240 | 8.75 |
| Central AC (3 ton) | 3,500 | 240 | 14.6 |
How to convert watts to amps
- DC (batteries, solar, 12 V systems): amps = watts / volts. 100 W at 12 V is 8.33 A.
- AC single-phase (house circuits): amps = watts / (volts x power factor). Use a power factor of 1 for heaters, kettles and incandescent lights. A motor load with a power factor of 0.8 draws more: 1,000 W at 120 V is 10.4 A instead of 8.33 A.
- AC three-phase: amps = watts / (1.732 x line-to-line volts x power factor). 10,000 W at 208 V with a power factor of 0.9 is 30.8 A per line.
- Amps to watts runs the same formulas the other way: watts = amps x volts (x power factor, x 1.732 for three-phase).
What size breaker do I need?
The National Electrical Code calls a load continuous when it runs at its full current for 3 hours or more. For those, the breaker has to be rated at least 125% of the load (NEC 210.20(A)), so a 12.5 A heater that runs all evening needs 15.6 A, which rounds up to the next standard size, 20 A. Separately, one plug-in appliance on a 15 or 20 A circuit may use no more than 80% of the circuit's rating (NEC 210.23(B)(1)). An electrician sizes new circuits; the wire gauge has to match the breaker, so never swap in a bigger breaker on its own.
Sources
Continuous-load rule, 80% plug-in limit and standard breaker sizes: NFPA 70, National Electrical Code, 2026 edition: Article 100 (continuous load, 3 hours or more), 210.20(A) (125 percent of the continuous load), 210.23(B)(1) (80 percent for one cord-and-plug appliance on a 15 or 20 A circuit; 210.23(A)(1) before the 2023 edition) and Table 240.6(A). Appliance watts: Honda generator wattage estimation guide, Champion Power Equipment generator wattage chart and Generac generator wattage worksheet. Watts = amps x volts: DOE Energy Saver (archived copy).