What the code says
The US standard is NFPA 72, the National Fire Alarm and Signaling Code, which absorbed the former NFPA 720 when NFPA withdrew it in 2018. NFPA's guidance for homes: "CO alarms should be installed in a central location outside each sleeping area and on every level of the home and in other locations where required by applicable laws, codes or standards." For the best protection, it says, interconnect all CO alarms, and follow the manufacturer's instructions for placement and mounting height. Choose an alarm listed by a recognized testing laboratory.
CPSC says the same in short: on each level of the home and outside sleeping areas, and not in attics or basements unless they include a sleeping area.
Where the sources disagree
Kidde, First Alert and CPSC give different answers on distance, height and the basement. These are the differences:
| Rule | Kidde | The other view |
|---|---|---|
| Distance from fuel-burning appliances | At least 15 ft (2024 guide); at least 5 to 15 ft (placement page) | First Alert CO710: no closer than 20 ft |
| Basement | Yes, on every level including the basement | CPSC: not unless it has a sleeping area |
| Mounting height | Anywhere from 6 in below the ceiling to 6 in above the floor | First Alert CO710: on the wall, at least 4 in below the ceiling |
The manual for your model decides, because the rules differ by brand and even between two pages from the same brand. Where the room allows it, 20 feet from fuel-burning appliances meets all three distance figures.
How far from a furnace, water heater or stove?
First Alert's CO710 manual says not closer than 20 feet from a furnace or other fuel-burning heat source, or a fuel-burning appliance such as a water heater, and not within 5 feet of any cooking appliance. Kidde's 2024 carbon monoxide guide says at least 15 feet from fuel-burning appliances; its placement page says at least 5 to 15 feet.
How high should a CO detector be?
There is no single height. Kidde says carbon monoxide "is almost the same density as air" and spreads evenly, so a wall-mounted alarm can go anywhere from 6 inches below the ceiling to 6 inches above the floor, and a ceiling-mounted one at least 6 inches from the wall. First Alert's CO710 is a wall unit that goes no closer than 4 inches to where the wall meets the ceiling.
Should you put a CO detector in the basement?
Kidde says yes: one on every level, including the basement. CPSC says not in a basement unless it has a sleeping area. If someone sleeps in the basement, both agree. State law can also decide it: NCSL's table shows Wisconsin requiring an alarm on each floor and in the basement of homes with an attached garage, a fireplace or a fuel-burning appliance.
Where not to put one
The First Alert CO710 manual rules out:
- garages, kitchens, furnace rooms, and dusty or greasy areas
- within 10 feet of a bath, shower, humidifier, dishwasher or laundry room
- anywhere colder than 40°F or hotter than 100°F
- turbulent air near fans, vents or open windows
Kidde adds dead air spaces and spots next to a window or door, and says its units work between 40°F and 100°F. CPSC rules out attics unless someone sleeps there.
How many CO detectors do you need?
At least one on every level and one outside each separate sleeping area. First Alert adds one in each bedroom for extra protection, and one at each end of a bedroom hallway longer than 40 feet. A two-story house with all the bedrooms on one upstairs hall needs at least one outside the bedrooms upstairs and one on the main floor, plus one in the basement if you follow Kidde or someone sleeps down there.
Which states require carbon monoxide detectors?
NCSL says most states have adopted requirements, which may come from statute, regulation or building code. Its table shows these:
| Where the rule comes from | States |
|---|---|
| State statute covering homes (29 states and DC) | AK, CA, CO, CT, DC, FL, GA, IL, IA, LA, ME, MD, MA, MI, MN, MT, NE, NH, NJ, NY, NC, OR, PA, RI, TN, VT, VA, WA, WV, WI |
| Adopted the International Residential Code, which has CO alarm rules for new homes | AL, GA, ID, IN, KY, LA, NM, ND, OH, OK, SC, VA, WY |
Many of those laws apply only to new construction, a sale, rentals, or homes with fuel-burning appliances or attached garages. Some set distances: Illinois requires an alarm within 15 feet of every sleeping room, and Florida (new construction since July 1, 2008) and Minnesota within 10 feet of each sleeping room. Those distances are to the bedrooms, not from appliances.
NCSL warns that its table may not reflect all requirements. Check with your state or local housing department before you rely on it.
Test it, and know the sounds
Test each CO alarm at least once a month and replace it when the manufacturer says to (NFPA). Change replaceable batteries every year (CPSC). If one starts beeping or chirping, see carbon monoxide detector beeping for what each pattern means.
It is worth getting right. NFPA, citing a CDC study of 2005 to 2018, says unintentional carbon monoxide poisoning not caused by fire leads to about 101,847 emergency room visits, 14,365 hospital stays and at least 430 deaths a year in the US.
More on carbon monoxide
More on safety
Sources
- Carbon Monoxide Safety, National Fire Protection Association (NFPA).
- NFPA 720 Standard Development (status: Withdrawn), NFPA. Withdrawal approved 2018-08-14.
- CO Alarms (Carbon Monoxide Information Center), CPSC.
- User's Manual, Carbon Monoxide Alarm, Model CO710 (10-year sealed battery, digital display), First Alert.
- A Comprehensive Guide to Carbon Monoxide (CO), Kidde, 2024-04-29.
- What's the Best Placement for Alarms?, Kidde.
- Carbon Monoxide Detector Requirements, Laws and Regulations, National Conference of State Legislatures (NCSL).